Sistemụ ule GDTL AC Resonant maka ndị na-emepụta ọkụ
Enwere ike iji usoro GDTL AC Resonant Test System maka ndị na-emepụta ihe site na ịhazigharị inductance nke reactor, ma ọ bụ na-edozi ụzọ ọrụ nke resonant ugboro nke usoro iji nweta resonance.Enwere ike iji ụzọ abụọ abụọ ahụ nweta resonance.N'ime usoro nkwalite voltaji, ọ bụrụ na ebe resonant na-apụ apụ, enwere ike ịchọta ya kpọmkwem site n'ụzọ nke ọma n'iji ya gee ntị ugboro ugboro, nke na-eme ka uru Q dị elu ma belata ikike ike na ibu arọ nke ngwa ule.
●Obere size, Mkpa ọkụ tụnyere otu voltaji larịị, otu ikike generator AC na-eguzogide voltaji ule equipment.Single akụrụngwa bụ ihe karịrị 60kg, mfe ịkwaga.
●Advanced ụkpụrụ nke dum set ngwaọrụ na ọhụrụ ugboro & inductance modulation technology, hụ na generator ike ugboro na-eguzogide voltaji ule chọrọ.Oke ngwa ngwa.
●Ejiri isi mmalite njikwa mgbanwe 20Hz-300Hz.Ezigbo nchebe na mmepụta ebili mmiri, nkwụsi ike dị elu.Na otutu ọrụ mode, ọ dị mfe ịrụ ọrụ.
●Ọkụ ọkụ nke 220V ma ọ bụ 380V, dị mma maka ị nweta ike na saịtị.
●Enwere ike ịchọta ebe Max.Q kpọmkwem site na ọnọdụ nke mbụ inductance modulation na mgbe e mesịrị ugboro modulation, iji zere resonance deviation n'ihi voltaji boosting;
●Nhazi na-agbanwe agbanwe na mgbatị siri ike.Zute ihe niile achọrọ nnwale capacitive n'ime sistemụ ike.
●Udị ule ugboro ike ma ọ bụ ụdị ule mgbanwe mgbanwe.
●Ọtụtụ ojiji, ọnụ ahịa bara uru.
●Egosipụta voltaji: 0 ~ 50kV (RMS) ma ọ bụ n'okpuru.
●Ugboro mmepụta: 45 - 300Hz.
●Ụdị ebili mmiri: ebili mmiri dị ọcha, THD ≤ 1%.
●Oke.ike: 2000kVA ma ọ bụ n'okpuru.
●Usoro ọrụ: na-aga n'ihu na-arụ ọrụ 15mins otu oge na mmepụta ike zuru oke.
●Ihe kacha mma: 10 - 40.
●Mmetụta mgbanwe ugboro ugboro: 0.1HZ, enweghị ike nke <0.05%.
●Ike ọkọnọ: 220V ma ọ bụ 380V ± 15%, 50HZ ± 5%.
GDTF- 100/50 | |
Ntinye voltaji (V) | 380 |
voltaji mmepụta (kV) | 0-50 |
Ike (kVA) | 100 |
Oke ngwa | Generator - ike ruo ala 0.07-0.13 μF |
10kV (300 mm²) eriri ≤ 1 km | |
Nhazi isi | 50kV/1A Fixed reactor 1 set |
50kV/1A na-agbanwe agbanwe reactor 1 set | |
Capacitive nkesa 50kV | |
GDTF-150/50 | |
Ntinye voltaji (V) | 380 |
voltaji mmepụta (kV) | 0-50 |
Ike (kVA) | 150 |
Oke ngwa | Generator - ike ruo ala 0.13-0.2 μF |
10kV (300 mm²) eriri ≤ 1.5 km | |
Nhazi isi | 50kV/1.5A Fix reactor 1 set |
50kV/1.5A na-agbanwe agbanwe 1 set | |
Nkesa capacitive 50kV | |
GDTF- 225/50 | |
Ntinye voltaji (V) | 380 |
voltaji mmepụta (kV) | 0-50 |
Ike (kVA) | 225 |
Oke ngwa | Generator--ike ruo ala 0.2-0.27 μF |
10 kV (300 mm ²) eriri ≤ 2.5 km | |
Nhazi isi | 50kV/1.5A Ntọala 2 setịpụ |
50kV/1.5A na-agbanwe agbanwe 1 set | |
Nkesa capacitive 50kV | |
GDTF- 360/60 | |
Ntinye voltaji (V) | 380 |
voltaji mmepụta (kV) | 0-60 |
Ike (kVA) | 360 |
Oke ngwa | Generator--ike ruo ala 0.27-0.33 μF |
Nhazi isi | 60kV/2A Fixed reactor 1 set |
60kV/2A na-agbanwe agbanwe reactor 1 set | |
Capacitive nkesa 60kV |