GD6900 Capacitance na Dissipation Factor Tester
GD6900 na-atụ ihe ikike na ihe nhụsianya dielectric (tgδ) nke akụrụngwa eletrik dị elu.Ọ na-arụkọ ọrụ ọnụ, akwa ule ule dielectric nke arụnyere, ọkụ na-agbanwe agbanwe ugboro ugboro, onye na-ebuli elu na onye nrụpụta ọkọlọtọ SF6.
A na-emepụta isi iyi voltaji dị elu site na inverter nke akụrụngwa, nke a na-eji maka nnwale nnwale mgbe nkwalite mgbanwe.Ọ bụrụ na ịtinye iko mkpuchi na ngwaọrụ njikwa okpomọkụ, enwere ike ịnwale ọnwụ dielectric nke mmanụ mkpuchi.
●Ngosipụta ihuenyo LCD metụ aka.
●Mmụba nguzogide mkpuchi: Module nnwale mkpuchi mkpuchi etinyere, nwere ike mepụta nguzogide mkpuchi (IR), nha absorption (DAR), nyocha polarization index (PI).
●mgbawa kalenda na nnukwu nchekwa dị n'ime.Chekwaa nsonaazụ nnwale dịka usoro oge siri dị, lelee ndekọ akụkọ ihe mere eme wee bipụta nsonaazụ ya.
●Enwere ike ibupu data akụrụngwa site na diski U.
●Ụdị nnwale ọtụtụ, yana ụdịdị n'ime voltaji dị elu, n'èzí elu voltaji, ọkọlọtọ ime, ọkọlọtọ mpụga, GST/UST, mkpali onwe onye.Enwere ike ịme ule ọkụ dị elu (karịa 10kV) ule ọnwụ dielectric na ọnọdụ nke ọkọlọtọ mpụga n'èzí nnukwu voltaji.
●Nwalee CVT zuru ezu akara (Capacitive Voltage Transformer) C1 na C2 dielectric ọnwụ na ike n'otu oge.Nwalee ogo mgbanwe CVT na ọdịiche akụkụ voltaji.
●Enwere ike tụọ ọnwụ dielectric na uru capacitance nke C0 na nsọtụ elu nke CVT site n'iji ụzọ mkpuchi azụ.
●Mgbama nlele ọsọ dị elu.A na-achịkwa ihe ntụgharị ntụgharị na sekit nlele n'ime digitized.A na-edozi voltaji mmepụta mgbe niile.
●LCR akpaka nha.Inductance, capacitance, nguzogide, akụkụ nwere ike tụọ ma gosipụta ya.
●Otutu nchebe nke mgbanwe voltaji ntinye, mmepụta mkpụmkpụ mkpụmkpụ, oke voltaji, nke dị ugbu a, okpomọkụ, nchekwa na ntụkwasị obi.Ka ọ dị ugbu a, ọ nwere ọrụ nyocha nke ala, na anabataghị nkwalite voltaji maka akụrụngwa na-abụghị ala.
●Ọ dịghị mkpa ịkwatu ụzọ HV iji tụọ ọnwụ dielectric na ikike nke CVT.
●Enwere ike ịgbanwe ugboro ugboro ka ọ bụrụ 50Hz, 47.5Hz/52.5Hz, 45Hz/55Hz, 60Hz, 57.5Hz/62.5Hz, 55Hz/65Hz.
Ọnọdụ ọrụ | -15 ℃ ~ 40 ℃ | RH <80% | ||||||
Ụkpụrụ mgbochi nnyonye anya | Ntughari ugboro ugboro | |||||||
Ịnye ọkụ | AC 220V± 10%, 50/60Hz | Enwere ike iji generator. | ||||||
Mmepụta voltaji dị elu | AC 0.5KV ~ 10KV (12kV nhọrọ) | Kwa 0.1kV | ||||||
izi ezi | 2% | |||||||
Oke.ugbu a | 200mA | |||||||
Ike | 2000VA | |||||||
Ike ịkpali onwe ya | AC 0V ~ 50V/15A | 50Hz, 60Hz otu ugboro 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Ugboro abụọ akpaaka | ||||||
Mkpebi | ihe: 0.001% | Cx: 0.001pF | ||||||
izi ezi | ∆tgδ: ± (agụ * 1.0%+0.040%) | |||||||
∆C x: ±(agụ *1.0%+1.00PF) | ||||||||
Oke nha | tgk | Enweghị oke | ||||||
C x | 15pF <Cx <300nF | |||||||
10KV | Cx <60 nF | |||||||
5KV | Cx <150 nF | |||||||
1KV | Cx <300 nF | |||||||
Nyocha CVT | Cx <300 nF | |||||||
Oke nha nha LCR | L>20H (2kV) | R>10KΩ(2kV) | ||||||
nha nha LCR | 0.1% | Mkpebi | 0.01 | |||||
Ogologo oke CVT | 10 ~ 10000 | |||||||
Ihe ruru CVT ziri ezi | 0.1% | |||||||
Mkpebi oke nke CVT | 0.01 | |||||||
Nguzogide mkpuchi | DC voltaji dị elu | 5-10kV | izi ezi | ± (2%* Ọgụgụ +10V) | ||||
Izi ezi nke IR | 100kΩ-1000GΩ: <5% (nwale voltaji na-erughị 250V) 100GΩ-1000GΩ: 10% (nwale voltaji na-erughị 10000V) | |||||||
Akụkụ | Isi nkeji: 350(L)×270(W)×270(H) | |||||||
Igbe ngwa ngwa: 350(L)×270(W)×160(H) | ||||||||
Ikike ebe nchekwa | Otu narị abụọ, USB flash disk ka akwadoro. | |||||||
Ibu | Isi ihe: 22.75Kg | |||||||
Igbe ngwa ngwa: 5.25Kg |
Onye nyocha | 1 set |
Ngwa ngwa | 1 ibe |
HV uhie ule ndu 8m | 1 ibe |
LV nwa ule ndu 8m | 1 ibe |
Ụdọ ọkụ 1.8m | 1 ibe |
CVT Njikọ ndu 5m | 1 ibe |
Oghere dị n'ala 2m | 1 ibe |
Bipụta akwụkwọ | 2 mpịakọta |
10A fuse | 3 iberibe |
Ntuziaka onye ọrụ | 1 oyiri |
Akụkọ ule ụlọ ọrụ | 1 oyiri |
Ngwa nhọrọ | |
Igwe nyocha mmanụ | 1 pc |
Onye na-ahụ maka ikpo ọkụ | 1 pc |
Na mmanụ ule cell na kpo oku njikwa, onye ọrụ nwere ike nwalee tan delta nke dielectric mmiri mmiri dị ka transformer mmanụ.
Onye na-ahụ maka ikpo ọkụ
Mmanụ mmanụ