GDKC-15 Series Circuit Breaker Analyzer
Igwe ọkụ eletrik dị elu bụ otu n'ime ihe nchịkwa kachasị mkpa na usoro ike.A na-eji usoro GDKC-15 iji nwalee njirimara ike nke eriri sekit sekit dị elu.Ọ dị mfe iji rụọ ọrụ, yana oke ziri ezi.
GDKC-15A | GDKC-15B | GDKC-15C | GDKC-15D | GDKC-15E | GDKC-15F | GDKC-15G | GDKC-15H | |
Kọntaktị igwe | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 |
Nguzogide mmechi | 6 | 6 | 6 | 6 | 6 | 6 | 6 | |
Kọntaktị eserese | 3 | 3 | 3 | 3 | 6 | |||
Ntọ ala nwere ngwụcha okpukpu abụọ | 3 | 3 | 3 | 6 | ||||
Nguzogide dị ike( resistor ntinye mbụ) | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
Nguzogide kwụ ọtọ | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
Nguzogide ala | 3 | 6 |
●Ọ dabara maka nnwale igwe nke ụdị SF6 ọ bụla, ngwa nchikota GIS, mgbanaka oghere na mmanụ ọkụ.
●Ike mgbochi nnyonye anya siri ike.Enwere ike ịnwale ya n'ụzọ ziri ezi na ọdụ ụgbọ ala 500KV.
●Accelerometer (nhọrọ), ihe mmetụta linear, rotary sensọ, dị mfe ịwụnye ma dị mfe.
●A na-enweta data niile nke nnwale njirimara nrụgharị igwe yana maapụ ebili mmiri kwekọrọ ka emechara ngbanwe ahụ otu ugboro.
●Chekwaa data ule ubi yana elekere ozugbo arụnyere, nke dabara maka ịchekwa na ịchekwa ụbọchị na oge ule.
●Na ihuenyo LCD 10.1inch, gosi data niile na maapụ, yana ọkụ ndabere, mgbanwe mgbanwe LCD na gbanyụọ ebe nchekwa.
●Ọrụ menu enyi na enyi, dị mfe iji.Iji ngwa nbipute arụnyere n'ime ka ibipụta nsonaazụ data niile ngwa ngwa.
●Ejiri ngwanro njikwa nyocha data, nke enwere ike iji PC rụọ ọrụ n'ịntanetị yana faịlụ usoro WORD.Enwere ike ịwepụta nsonaazụ ule n'ụdị ọ bụla nke ndị na-ebi akwụkwọ na-ebipụta akụkọ nyocha iji mee ka nnwale ubi ahụ bụrụ kọmputa.
●Mepee ma mechie nhọrọ ọsọ ọsọ yana ọrụ akọwapụtara onye ọrụ dabere na mkpa, dabara maka nha ọsọ nke ụdị mgba ọkụ ọ bụla.
●Oge:
Oge emeghe (emechi) kọntaktị 12
Na mmekọrịta nke ngalaba
Mmekọrịta usoro-na-ọsọ
●Na-emechi:
CO, OC, oge COC,
Oge mmeghe nke mbụ, oge mmechi mbụ, oge nke abụọ, oge imeghe, oge anwụ, enweghị oge ugbu a.
●Na-agbapụ:
Mechie oge ibiaghachi, oge, usoro na ụdị ifegharị kọntaktị ọ bụla.
Ngosipụta nkwụghachi ụgwọ nke kọntaktị ọ bụla.
Ọsọ ọsọ: ọsọ na kọntaktị naanị imeghe na naanị mmechi, oke ọsọ kacha, ogologo oge njirimara njem.
Njem: mkpokọta njem, oghere oghere, ngafe njem, njem nlegharị anya, njupụta nkwụghachi.
Ugbu a: meghe/ mechie ugbu a, eserese ebili mmiri dị ugbu a nke igwe meghe/emechi.
Voltage na-arụ ọrụ: DC0 ~ 300V / 20A dijitalụ arụnyere, isi iyi ike na-agbanwe agbanwe, na-akpaghị aka zuru ezu ule ọrụ LV nke onye na-emebi sekit wee tụọ uru voltaji nke onye na-emebi sekit.
Nguzogide mmechi: oge nkedo, pre-pitch waveform na uru nguzogide nke mmechi mmechi nke kọntaktị 6.(nhọrọ)
Kọntaktị eserese: oge mepere emepe, oge mmechi na ụdị ebili mmiri siri ike nke mgba ọkụ kọntaktị Siemens graphite nwere kọntaktị ụzọ 3 ma ọ bụ 6. (nhọrọ)
Nkwụsị ala okpukpu abụọ: n'okpuru ọdụ ụgbọ mmiri 3 ma ọ bụ 6, ọ nwere ike tụọ oge mmeghe na mmechi nke ọma.(nhọrọ)
Nkwụsi ike kwụ ọtọ: 1 * 100A nguzogide nguzogide kọntaktị.
Nguzogide na-agbanwe agbanwe (Onye na-ebu ụzọ ntinye): 1 * 100A mgbanwe mgbanwe nke nguzogide ike n'oge ihe nbibi sekit.
●Ojiji gburugburu
Ike ntinye: 220V± 10%, 50Hz±10%, Nrụgide ikuku: 86-106kpa
Okpomọkụ: -10-40℃ iru mmiri: ≤80% RH
●Arụmọrụ nchekwa
Mgbochi mkpuchi>2MΩ
Ike Dielectric: Shell nwere ike iguzogide voltaji ugboro ugboro 1.5kV na nkeji 1 na-enweghị flashover na arcing.
●The Basic Parameter
Oge: Oke 20000.0ms, mkpebi 0.01ms, njehie 0.5%
Nguzogide mmechi: oke 10kΩ, min.mkpebi 1Ω, njehie 0.5% (nhọrọ)
Kọntaktị eserese: nso 200ms, min.mkpebi 0.1ms, njehie 0.5% (nhọrọ)
Ntọ ala nwere ngwụcha abụọ: oke 200ms, min.mkpebi 0.1ms, njehie 0.5% (nhọrọ)
Nguzogide kwụ ọtọ: oke 1uΩ~10mΩ, min.mkpebi 0.01μΩ, njehie 0.5%
Nguzogide dị ike: oke 10mΩ, min.mkpebi 1μΩ, njehie 0.5%
Nwale ugbu a: DC 50A, 100A (3 agba tụrụ n'otu oge)
Ọsọ: Mkpebi 20.00m/s 0.01m/s njehie 0.5%
Njem:
Ụdị | Oke | Mkpebi | Njehie |
Ihe nkwụsịtụ | 50.0mm | 0.1mm |
0.5% |
SF6 mgbawa sekit | 300.0mm |
1mm | |
Mmanụihe mgbawa sekit | 600.0mm |
Ugbu a: oke 20.00A, mkpebi 0.01A
Ike mmepụta: DC 0-300V dijitalụ mgbanwe/20A (na-arụ ọrụ ozugbo), mkpebi 1V.
Akụkụ: ihe dịka 360mm (L)* 280mm (W)* 300mm (H)
Arọ: ihe dịka 10kg
Isiunit ya na mbadamba 10.1-inch | 1 pc |
Ngwa ngwa | 1 pc |
Chaja maka mbadamba nkume | 1 pc |
American ọkọlọtọ nkwụnye | 2 pcs |
Rotary ihe mmetụta ọsọ | 1 pc |
Ihe mmetụta ọsọ ọsọ Linear50mm | 1 pc |
Igwe njikọ mgbama ọsọ ọsọ (5-waya echedoro isi) | 1 pc |
Igwe njikwa mmeghe na mmechi(3-eriri sheathed core) | 1 pc |
Mkpalite mpụgana-achọpụtaeriri (uhie/oji, 2-isi) | 1 pc |
eriri ala | 1 pc |
Igwe nyocha kọntaktị(4-eriri sheathed core) | 1pc |
Contact ule ogologo eriri USB (5M, odo, akwụkwọ ndụ akwụkwọ ndụ na uhie nke ọ bụla otu ibe, ojii 3pcs) | 6pcs |
Eriri obere eriri (0.5m ojii,2m nwa) | 2 pcs |
Ụdọ ọkụ | 1 pc |
Ihe jikọrọ Universal na ntọala magnet | 1 setịpụrụ |
Ngwa nrụnye pụrụ iche | 1 set |
Nwalee obere vidiyo na thimbles | 18 pcs |
Ckọntaktị na-eguzogide ule cable(5M) | 1 pc |
Bipụta akwụkwọ | 2 mpịakọta |
eriri USB | 1 pc |
Ntuziaka onye ọrụ | 1 pc |
Akuko ule ụlọ ọrụ | 1 pc |