Ka ikike nke ngwaahịa a nwalere na-abawanye yana mmeghachi omume ntanye nke ihe ngbanwe ule, ka ahụ ka mmetụta ịrị elu capacitance pụta ìhè.Ya mere, mgbe anyị na-eme AC na-anagide voltaji ule nke usoro resonance nnukwu-ikike ule ihe, ọ na-achọrọ ka tụọ voltaji na njedebe nke ule ihe iji gbochie ule ihe n'okpuru oke voltaji.
HV Hipot GDTF-800kVA/400kV AC Resonant Test System
Ihe nrịba ama nke ngwaọrụ nnwale resonance usoro bụ ihe ndị a kpatara:
(1) A na-agbanye ikuku nke mbụ na mberede kama iji nwayọọ nwayọọ na-abawanye site na voltaji efu.
(2) Mgbe a ka nwere voltaji dị elu, bepụ ọkụ eletrik na mberede, kama ịdaba na efu ma bepụ voltaji.Enwere ike ịhụ site na usoro mgbanwe nke ntụgharị ntụgharị na ọnọdụ abụọ dị n'elu ga-eme ka oke ọkụ na ngwaahịa a nwalere, nke na-adịghị ekwe.
Maka (1) igbochi site na sekit njikwa iji gbochie nrụgide na-abụghị efu efu na mberede.
Maka (2) ekwesịrị itinye usoro arụ ọrụ ziri ezi iji zere.
(3) Akụkọ ule na-ada na mberede.Nke a na-ezutekarị na nke a na-apụghị izere ezere.Ọ bụrụ na a na-ejikọta njedebe nkwụsị nke ihe ngbanwe ule na ngwaahịa a nwalere, mgbe ngwaahịa a nwalere na-akụda na mberede, ikike nke njedebe nkwụsị nke ihe ngbanwe nke ule na-amanye ozugbo ka ọ bụrụ efu, nke ya na ihe mberede mere na nkwụsịtụ ahụ. ọgwụgwụ nke ule transformer—otu ife n'ihu dị nnọọ steepụ Uru kacha elu nke mkpali voltaji ifegharị bụ hà nhata ozugbo uru nke ozugbo ule voltaji nke ule ihe, ma polarity bụ megidere.Nke a ga-ebute oke ọkụ dị ize ndụ na mkpuchi ogologo nke windings transformer test.
Ụzọ iji gbochie ya bụ jikọọ a na-echebe resistor na kwesịrị ekwesị iguzogide uru na usoro n'etiti transformer tinyekwa ọgwụgwụ nke ike ugboro usoro resonance ule ngwaọrụ na ule ihe, nke mere na mkpali voltaji nke megidere polarity eme na usoro sekit nke. ndị na-echebe resistor na transformer mbata capacitance.Maka obere oge, ọtụtụ voltaji na-adaba na ihe mgbochi nchebe.