●Full ọrụ na ike na-egbo ụdị nile nke CT (nchedo CT, atụ CT, TP) ule chọrọ, dị ka excitation e ji mara ule, ntụgharị ruru, polarity, secondary winding iguzogide, secondary ibu, ruru njehie, angular iche na wdg nwekwara ike ji mee ihe. iji nwalee excitation e ji mara, ntụgharị ruru, polarity, nke abụọ winding eguzogide, ratio njehie, angular iche na wdg niile di iche iche nke PT.
●Nkwenye n'ọhịa nke CT anaghị achọ ihe ntụgharị ọkọlọtọ ugbu a, injector dị ugbu a, ụlọ akụ ibu, njikwa njikwa voltaji na nnukwu eriri ugbu a.A na-eji wiwi ule dị mfe na ịrụ ọrụ iji ghọta nkwenye nke transformer ugbu a, nke na-ebelata oke ọrụ ma na-eme ka arụmọrụ ọrụ dịkwuo mma, ma na-eme ka nkwenye dị n'ọhịa dịkwuo mma.
●Nyochaa nke ọma njehie oke na ọdịiche angular, njehie kacha ekwe omume nke njehie oke bụ ± 0.05%, na njehie kacha nke angular dị iche bụ ± 2min.Ọ nwere ike tụọ 0.2S larịị transformer ugbu a, na nha nha nha bụ 1 ~ 40000.
●Dabere na usoro ntụgharị ugboro ugboro dị elu iji nwalee CT/PT voltaji-ụkpụrụ njirimara ugbu a yana usoro njehie 10%, enwere ike ịpụtapụta oke AC voltaji nke 180V na AC ugbu a nke 12Arms (36A peak) mana ọ nwere ike ịnagide ule CT. nke ikpere ruo 60KV.
●Nnwale akpaaka CT/PT paramita dị ka ikpere n'ókè voltaji/ugbu a, 5% na 10% njehie usoro, ziri ezi ókè ihe (ALF), nchekwa ihe (FS), secondary time constants (Ts), magnetik remanence coefficient (Kr), juputara. na unsaturated inductance.
●Nnwale a zutere ụdị ngbanwe dị iche iche dịka GB1208 (IEC60044-1), GB16847 (IEC60044-6), na GB1207, a na-ahọrọ ụkpụrụ ule na-akpaghị aka dabere n'ụdị na ọkwa nke transformer.
●Nnwale ahụ dị mfe ma dị mma.Enwere ike mechaa nguzogide CT DC, mkpali, oke na polarity site na otu igodo.E wezụga ule ibu, ule niile nke CT na-enweta otu ụdị wiring.
●5.7-inch graphic LCD transflective, a na-ahụ nke ọma na anyanwụ.
●Ejiri òké anya na-atụgharị anya na-arụ ọrụ, ọrụ ahụ dị mfe, ngwa ngwa na adaba, ma dị mfe ịmụta.
●Ngwa nbipute arụnyere n'ime ya, na-ebipụta akụkọ nnwale emepụtara na-akpaghị aka.
●Enwere ike ibupụ nsonaazụ ule ahụ site na diski U, enwere ike ịkwalite mmemme ahụ na diski U, nke dị mma na ngwa ngwa.
●Chekwaa data otu 1000 ma ọ naghị efu mgbe ọkụ kwụsịrị.
●Ejiri ya na ngwanrọ nyocha ndabere iji kwado nchekwa, ntụgharị na nyocha nke akụkọ nyocha, enwere ike iji ya tụnyere, ikpe na nyocha nke data ule.
●Ọ dị mfe iburu, arọ ngwaọrụ <10kg.